Sample lesson · Module 2, Weak grids and SCR · about 12 minutes
What happens as the grid gets weaker
Stable
Illustrative model, not an EMT result.
Every connection point has a fault level
It is the apparent power the grid would feed into a short circuit at that point. A stiff grid delivers a lot. A grid at the end of a long line delivers little.
The plant in the figure is rated 150 MW. It connects where the fault level is 450 MVA.
Divide the two: the short-circuit ratio
450 MVA150 MW=3.0
At this ratio the grid counts as medium.
Above 3 a grid counts as strong, from 2 to 3 as medium, from 1 to 2 as weak, and below 1 as very weak. Some sources draw the lines elsewhere.
Drag grid strength under the figure and watch the fault level.
First, a prediction
Seen from the plant, the grid is a voltage source behind an impedance. When SCR goes down, that impedance is:
The converter pushes current into the grid
A grid-following converter behaves as a controlled current source. It measures the grid voltage and places its current relative to it.
The moving dots in the figure are that current, on its way to the grid.
That current moves the voltage
On its way the current crosses the grid reactance, and the voltage at the connection point shifts. The bigger the reactance, the bigger the shift.
Right now a 0.10 pu change in reactive current moves the voltage by about … pu.
Take grid strength down to 2 or below and watch that number.
The PLL ends up chasing itself
To place its current, the converter tracks the angle of the voltage with a Phase-locked loop (PLL). A control loop that tracks the angle of the grid voltage, so the converter knows where to place its current..
On a weak grid that voltage is partly the converter's own doing. Its current shifts the angle, the PLL follows, and the current moves again. A loop that feeds itself can ring, or grow.
Now weaken the grid yourself
The scope shows the voltage at the connection point after a small disturbance. How fast the swing dies away is its damping, and the third meter puts a number on it.
Drag grid strength down until the verdict changes from Stable.
There. The oscillation still dies out, but it takes far longer. Keep going down if you want to see it grow.
Two grids on one screen
Press Hold this trace, at the top of the scope. Then take grid strength from 3 down to about 2.
The held trace stays as a dashed line, so you can compare the two.
A third less grid strength, and the damping ratio has dropped to well under half. The margin does not shrink in step with the grid. It collapses near the limit.
Find the limit
Below roughly which SCR does this model lose stability? Use the figure.
Read the damping
What is the damping ratio at SCR 2.0? Three decimals.
Why this is only a sketch
The figure runs a simple second-order model, shaped to show the trend. It is right about the direction and unreliable about the numbers.
In a real plant the limit depends on the controller tuning, the grid's X/R ratio, neighbouring converters, and current limits and protection.
Answering it properly takes an electromagnetic transient (EMT) simulation: full waveforms, controls at their real speed. That is what you do in PSCAD in the program, and why grid operators ask for EMT models of converter plants.
What you just worked out
- SCR is the fault level divided by the plant's rating, and the grid reactance in per unit is about 1 / SCR.
- On a weak grid the converter's own current moves the voltage its PLL is tracking.
- Damping does not fall in step with grid strength. It collapses near the limit.
Checkpoints answered correctly: 0 of 2. This sample does not store anything. In the program every checkpoint counts toward your score.
This was one lesson. The program has seven modules, four PSCAD labs and a capstone. It runs from 1 February 2027 to 31 March 2027.
Apply by 15 January 2027Placeholder: the application form is not linked yet.
Further reading. CIGRE Technical Brochure 671, Connection of wind farms to weak AC networks, 2016. Text and figure are PGE's own.